Why a Pipeline Pump Will Not Pump: Air Binding and Priming

What is air binding?
A centrifugal pump moves water by spinning it. Air is around 800 times lighter than water, so if the casing is full of air the impeller spins it without creating enough pressure difference to draw water in. The pump runs, warms up and delivers nothing.
How do I prime the pump?
- With a flooded suction, open the suction valve and the vent on the pump until water comes out without bubbles.
- With a suction lift, fit a foot valve with a strainer on the suction pipe and fill the pipe and casing with water before starting.
- Close the vent, then start the pump with the discharge valve partly open.
Why does it lose prime later?
- Air leaking in at a suction joint or a worn seal
- A foot valve that leaks back when the pump stops
- The water level falling until a vortex draws air into the suction
Why should it not run dry?
The mechanical seal relies on the liquid to cool and lubricate its faces. Running without water can damage it in a short time.
Products in This Series
Pipeline Centrifugal Pumps & CDL Multistage PumpsPipeline Pumps for HVAC Chilled and Condenser Water Circulation
Vertical inline pumps for chilled water and condenser water loops in HVAC systems: what sets the flow and head, and why closed-loop pressure matters.
Pipeline Centrifugal Pumps & CDL Multistage Pumps60 Hz and Special Voltage Pipeline Pumps and CDL Multistage Pumps
Pipeline and multistage pumps for 60 Hz and 380, 440 or 460 V supplies. Why a 50 Hz pump overloads on 60 Hz and what to send us.
Pipeline Centrifugal Pumps & CDL Multistage PumpsA, B and C Trimmed Impellers: Matching a Pipeline Pump to the Duty
The A, B and C at the end of a pipeline pump model mark trimmed impellers. How trimming lowers head and power, with the 40-250(I) family as an example.
Need a pump for your application?
Our engineers respond to technical inquiries within 24 hours.
Get a Quote