High-Rise Water Boosting with a CDL(F) Multistage Pump: Worked Example

The building
- 25 floors, about 3 m each: top outlet about 75 m above the pump
- Peak demand for the zone: 16 m³/h
- Wanted pressure at the top outlet: about 15 m (0.15 MPa)
- Pipe and fitting losses at peak flow: about 10 m
The head
75 m lift + 10 m losses + 15 m at the top outlet = 100 m. If the pump draws from a tank with water above it, subtract that height; if it lifts from below, add it.
The pump
At 16 m³/h, the CDL(F) 16 family applies. The CDL(F) 16-80 gives 94 m, a little short; the CDL(F) 16-90 gives 106 m with an 11 kW motor and covers the duty.
In practice
- Booster sets usually use two or three pumps with a variable frequency drive, so one pump covers low demand quietly
- Very tall buildings are split into pressure zones so the lower floors are not over-pressurised
- Keep the pump’s own suction side flooded from the tank
Compare other stage counts in the CDL(F) selection table.
Products in This Series
Pipeline Centrifugal Pumps & CDL Multistage PumpsPipeline Pumps for HVAC Chilled and Condenser Water Circulation
Vertical inline pumps for chilled water and condenser water loops in HVAC systems: what sets the flow and head, and why closed-loop pressure matters.
Pipeline Centrifugal Pumps & CDL Multistage Pumps60 Hz and Special Voltage Pipeline Pumps and CDL Multistage Pumps
Pipeline and multistage pumps for 60 Hz and 380, 440 or 460 V supplies. Why a 50 Hz pump overloads on 60 Hz and what to send us.
Pipeline Centrifugal Pumps & CDL Multistage PumpsA, B and C Trimmed Impellers: Matching a Pipeline Pump to the Duty
The A, B and C at the end of a pipeline pump model mark trimmed impellers. How trimming lowers head and power, with the 40-250(I) family as an example.
Need a pump for your application?
Our engineers respond to technical inquiries within 24 hours.
Get a Quote