Sizing a Heating Circulation Pump from the Heat Load

Step 1: flow from the heat load
Water carries about 1.163 kWh per cubic metre for each degree of temperature change. So the flow in m³/h is the heat load in kW divided by 1.163 times the temperature drop across the system.
Example: a 500 kW heating system designed for a 10 °C drop between supply and return. Flow = 500 ÷ (1.163 × 10) ≈ 43 m³/h.
Step 2: head from the loop resistance
Add up the pressure losses through the boiler or heat exchanger, the pipes, valves and the worst-placed radiator or coil. In a closed loop the height of the building does not count, because the water coming down balances the water going up. Say the total comes to 18 m.
Step 3: choose the pump
43 m³/h at 18 m points to an 80 mm frame. The 80-125 is rated 50 m³/h at 20 m with 5.5 kW, and covers the duty with a small margin. For hot water, it is built as an IRG.
Then check
- The highest water temperature, which decides the seal
- Static plus pump pressure, within 1.6 MPa
- NPSH at the hottest water, especially if the pump sits near the boiler outlet
All frames are in the selection table.
Products in This Series
Pipeline Centrifugal Pumps & CDL Multistage PumpsPipeline Pumps for HVAC Chilled and Condenser Water Circulation
Vertical inline pumps for chilled water and condenser water loops in HVAC systems: what sets the flow and head, and why closed-loop pressure matters.
Pipeline Centrifugal Pumps & CDL Multistage Pumps60 Hz and Special Voltage Pipeline Pumps and CDL Multistage Pumps
Pipeline and multistage pumps for 60 Hz and 380, 440 or 460 V supplies. Why a 50 Hz pump overloads on 60 Hz and what to send us.
Pipeline Centrifugal Pumps & CDL Multistage PumpsA, B and C Trimmed Impellers: Matching a Pipeline Pump to the Duty
The A, B and C at the end of a pipeline pump model mark trimmed impellers. How trimming lowers head and power, with the 40-250(I) family as an example.
Need a pump for your application?
Our engineers respond to technical inquiries within 24 hours.
Get a Quote