Pipeline Centrifugal Pumps & CDL Multistage PumpsSizing a Heating Circulation Pump from the Heat Load
How to get the flow of a heating circulation pump from the heat load and temperature drop, with a worked example and the pipeline pump that fits.

Model: CDL(F) 16-90
Working out the head for a high-rise booster pump and choosing a CDL(F) build: a 25-floor example at 16 m³/h, step by step.
| Flow Rate | 16 m³/h |
|---|---|
| Head | 106 m |
| Power | 11 kW |
| Inlet / Outlet Diameter | DN50 |
| Material | Stainless steel wetted parts |
Not sure this pump fits your duty? Try the pump selector
75 m lift + 10 m losses + 15 m at the top outlet = 100 m. If the pump draws from a tank with water above it, subtract that height; if it lifts from below, add it.
At 16 m³/h, the CDL(F) 16 family applies. The CDL(F) 16-80 gives 94 m, a little short; the CDL(F) 16-90 gives 106 m with an 11 kW motor and covers the duty.
Compare other stage counts in the CDL(F) selection table.
Pipeline Centrifugal Pumps & CDL Multistage PumpsHow to get the flow of a heating circulation pump from the heat load and temperature drop, with a worked example and the pipeline pump that fits.
Pipeline Centrifugal Pumps & CDL Multistage PumpsVertical inline pumps for chilled water and condenser water loops in HVAC systems: what sets the flow and head, and why closed-loop pressure matters.
Pipeline Centrifugal Pumps & CDL Multistage PumpsPipeline and multistage pumps for 60 Hz and 380, 440 or 460 V supplies. Why a 50 Hz pump overloads on 60 Hz and what to send us.